Options
Impact of Earthing System Designs and Soil Characteristics on Tower Footing Impedance and Ground Potential Rise: A Modelling Approach for Sustainable Power Operation
Journal
Sustainability
Date Issued
2021
Author(s)
Nur Alia Farina Mohamad Nasir
Mohd Zainal Abidin Ab Kadir
Miszaina Osman
Muhamad Safwan Abd Rahman
Ungku Anisa Ungku Amirulddin
Mohd Solehin Mohd Nasir
Nur Hazirah Zaini
Nik Hakimi Nik Ali
DOI
10.3390/su13158370
Abstract
Improving a tower earthing system by reducing the impedance is an effective solution to prevent back flashover from occurring and thus maintaining the sustainable operation of power supply. Knowledge of the soil and earthing structure is an important element when designing an earthing system and to determine the parameters of a transmission line (TL). This paper presents the computation of soil structure interpretation based on several earthing designs using current distribution, electromagnetic interference, grounding, and soil structure analysis (CDEGS) software. The results showed that each tower has a multi-layer soil structure and it was also found that the soil resistivity at the surface layer strongly affected the earthing impedance. Subsequently, it was demonstrated that soil structure and the earthing design arrangement are the two parameters that significantly affected the ground potential rise (GPR). This aspect affects the resistance and impulse impedance of a tower and thus influences the performance of the TL system when subjected to lightning strike, which is undoubtedly one of the major culprits of power outages in Malaysia.
Subjects
File(s)
Loading...
Name
43. Impact Of Earthing System Designs And Soil Characteristics On Tower Footing Impedance And Ground Potential Rise.pdf
Size
2.29 MB
Format
Adobe PDF
Checksum
(MD5):dc16193255cd79982855be43b77378cf